Tiêu chuẩn cấp gió tươi và thông gió điều hòa .Singapor standard SS CP13 : 1999 




Code of practive for mechanical ventilation and air -conditionning in buidings.

Table 1 - Outdoor air supply requirement for comfort air-conditioning
Type of buiding/

Occupancy
Minimum outdoor air supply

L/s per floor area
m³/h per m² floor area
Restaurants
2.80
10.00
Dance halls
5.30
19.00
Ofiices
0.65
2.30
Shop, supermarkets and

department stores
1.00
3.60
Lobbies, concourses and corridors
0.25
0.90
Classrooms 
2.60
9.20
Theatres and cinemas
2.00
7.30
Factories and workshops
Light
1.20
4.30
Medium
0.70
2.60
High
0.35
1.30
Hotel guest rooms
15 L/s per room
54 m³/h per room


Table 2- Outdoor air supply for mechanical ventilation in non-conditioned buidings
Type of buiding

Occupancy
minimum outdoor air supply

Air-change/h
Ofiice
6
Restaurant ,canteens
10
Shop, supermarkets and department stores
6
Workshops ,factories
6
Classrooms
8
Theatres and cinemas
8
Lobbies ,concourse , conffidors , staircases and exit
4
Tolets , bathrooms
10
Kitchens (commercial ,institutional and industrial
20
Car Parks
6
Fire commmand center
6
Civil Defence shelters
16
Wasterwater facilities/pumping installation
8